software upgrade is performed from Doors.NET software revisions prior to v3.5.1.18.
This results in increasing network communication degradation as the number of master
controllers increases. To correct this issue the Controller Timeout and Network Timeout
values must be changed to the optimum values.
1. Click Setup > Hardware Setup
2. Expand the Communication Channel tree
3. Select the Network Channel
4. In the grid change the Controller Timeout value to 20,000 (previous default value
was 800)
5. In the grid change the Network Timeout value to 20 (previous default value was 5)
6. Save these changes