10. Highlight the reader for Door 2 and again locate the Anti-Passback settings.
l Anti-Passback Mode - must be set to Hard
l Enter Area - must be set to Door 2 (or the name assigned to the second area)
l Exit Area must be set to Door 1 (or the name assigned to the first area)
11. The Airlock setup/configuration is then complete, so the next step is to present a
valid card at Door 1, then open the door contact when access is granted.
12. With the door contact still open for Door 1, present the same card to Door 2 - You
will get Access Denied and in Live Events the full message will be:
13. You will only be able to get access at Door 2 again when the Door 1 door contacts
are in the closed state.
14. And you will only be able to get access through Door 1 when the contacts for Door
2 are closed.